12/24 / 40.5kV Guhindura isi
Imikorere isanzwe
1. Uburebure bw'inyanja butarenga 1000m;
2. Ubushyuhe bwikirere bwikirere: + 45 ℃, -25 ℃;
3. Imbaraga z’ibiza zitarenza dogere 8;
4. Ubushuhe bujyanye nuburinganire buri munsi butarenze 95%, impuzandengo ya buri kwezi ntabwo irenga 90%;
5. Icyiciro cyanduye: II
Imiterere yihariye: Nyamuneka sobanura igihe utumiza.
12kv Mu nzu Yumuvuduko mwinshi Ac Guhindura ibintu
Ibyingenzi Byubuhanga
Ibintu | Igice | Amakuru | ||
Ikigereranyo cya voltage | kV | 12 | ||
Ikigereranyo kigufi-cyihangane nubu | kA | 31.5 | ||
Ikigereranyo kigufi-cyumwanya | s | 4 | ||
Ikigereranyo kigufi-kizunguruka gifunga umuyaga | kA | 80 | ||
Ikigereranyo cyo hejuru cyihanganira ikigezweho | kA | 80 | ||
Urwego rwo kugereranya | Ikigereranyo cyigihe gito | kV | Icyiciro ku isi / hagati yicyiciro | 42 |
Ikigereranyo cyo kumurika impulse ihangane na voltage | 75 | |||
Kwihangana kwa mashini | Ibihe | 2000 |
Ibisobanuro bya tekiniki
GPJN15-12 / 31.5 Urupapuro rwerekana ibintu hamwe nuburinganire
GPJN15A-12 / 31.5 Imiterere yubutaka bwimiterere nubunini bwubushakashatsi
24kv Mumazu Yumuvuduko mwinshi AC Guhindura ibintu
Amakuru yingenzi ya tekiniki
Ibintu | Igice | Amakuru | ||
Ikigereranyo cya voltage | kV | 24 | ||
Ikigereranyo kigufi-cyihangane nubu | kA | 31.5 | ||
Ikigereranyo kigufi-kizunguruka gifunga umuyaga | kA | 80 | ||
Ikigereranyo cyo hejuru cyihanganira ikigezweho | kA | 80 | ||
Ikigereranyo kigufi-cyumwanya | s | 4 | ||
Urwego rwo kugereranya | 1min Imbaraga zingufu zihanganira voltage | kV | Icyiciro ku isi / hagati yicyiciro | 65 |
Kumurika impulse kwihanganira voltage | 125 | |||
Kwihangana kwa mashini | ibihe | 2000 |
GPJN15-24 / 31.5 Urupapuro rwerekana ibintu hamwe nuburinganire
40.5kv Mu nzu Yumuvuduko mwinshi AC Guhindura ibintu
Amakuru yingenzi ya tekiniki
Ibintu | Igice | Amakuru | ||
Ikigereranyo cya voltage | kV | 36/38 / 40.5 | ||
Ikigereranyo kigufi-cyihangane nubu (4s) | kA | 31.5 | ||
Ikigereranyo kigufi-kizunguruka gifunga umuyaga | kA | 80 | ||
Ikigereranyo cyo hejuru cyihanganira ikigezweho | kA | 80 | ||
Intera yicyiciro | mm | 300, 350, 400 | ||
Urwego rwo kugereranya | (1min) Imbaraga zumuriro zihanganira voltage | kV | Icyiciro ku isi / hagati yicyiciro | 95 |
Kumurika impulse kwihanganira voltage | 185 |
Urucacagu no kugereranya
GPJN15-12 (24) (40.5) kV Guhindura moteri ya moteri
GPJB sisitemu y'amashanyarazi.Birakwiriye kuri 3 ~ 40.5KV, icyiciro 3, AC 50 (60) Hz sisitemu yubwoko bwubwoko bwamashanyarazi menshi.Irakoreshwa muburyo bwo guhinduranya amashanyarazi menshi nkubutaka bwo kurinda iyo kubungabunga.
Imikorere y'ibicuruzwa yujuje GB1985-2004 Umuyoboro mwinshi wa AC Umuyoboro wa AC hamwe na Earthing Switch hamwe nibisabwa mubisanzwe kimwe na IEC62271-102: 2002.
Imiterere yubutaka iroroshye kandi yoroheje, uburemere bworoshye, imikorere yoroheje, kwishyiriraho byoroshye, imbaraga zumuriro uhamye, hamwe nigikorwa cyamashanyarazi cyizewe, komeza imiyoboro yumwimerere mugufata urukwavu rwimyenda ihoraho, byabaye patenti yigihugu.
Ibicuruzwa Icyitegererezo Nicyo gisobanura
Ibipimo fatizo
Icyitegererezo cyibicuruzwa | GPJN15 | ||||
Ikigereranyo cya voltage ikora | 12kV | 24kV | 40.5kV | ||
Ikigereranyo kigufi-cyihangane current 4S) | 31.5kA | 40kA | 50kA | 31.5kA | |
Ikigereranyo cyo hejuru cyihanganira ikigezweho | 80kA | 100kA | 125kA | 80kA | |
Ikigereranyo kigufi-kizunguruka gifunga umuyaga | 80kA | 100kA | 125kA | 80kA | |
Urwego rukingira: | Inzira nyamukuru irwanya voltage (1min) | 42kV | 65 kV | 95kV | |
Ikigereranyo cyo kumurika impulse ihangane na voltage | 75kV | 125 kV | 185kV | ||
Hafi yintera nyuma yo gufungura bitari munsi | 125mm | Mm 200 | 300mm | ||
Kugenzura voltage | AC220V | DC220V | DC110V |