40.5kV SF6 Kumena Inzira GPFN Urukurikirane
Icyitegererezo n'Ubusobanuro
![4](http://www.gpswitchgear.com/uploads/414.jpg)
Koresha Ibidukikije
a.Uburebure: ntiburenze 1000m
b.Ubushyuhe bwibidukikije: -15 ℃ ~ + 40 ℃, ubushyuhe bwa buri munsi ntiburenga + 35 ℃
c.Ubushuhe bwibidukikije: Ubushyuhe buri munsi ugereranije: ≤95% buri kwezi ugereranije ugereranije nubushuhe: ≤ 90%
Impuzandengo ya buri munsi yumuvuduko wumwuka: ≤2.2x10-3 MPa Ukwezi kwikigereranyo cyumuvuduko wumuyaga: ≤1.8x10-3MPa
d.Imbaraga z’umutingito: ntizirenza dogere 8
e.Aho ukoreshwa: Umwuka w’ibidukikije ntushobora kwanduzwa cyane n ivumbi, umwotsi, ibora kandi / cyangwa imyuka yaka umuriro, imyuka cyangwa igihu cyumunyu.
Icyitonderwa: Mugihe ibidukikije byakoreshejwe bidahuye nibi byavuzwe haruguru, nyamuneka ubaze ikigo cyacu.
Ikigereranyo cya tekiniki
Oya. | Ibintu | Igice | Amakuru | |||
1 | Ikigereranyo cya voltage | kV | 40.5 | |||
2 | Ikigereranyo cyagenwe | Hz | 50 | |||
3 | 1min power frequency kwihanganira voltage | Hagati yinkingi, Kwisi | kV | 95 | ||
Ivunika | 118 | |||||
Inkuba kwihanganira voltage | Hagati yinkingi, Kwisi | 185 | ||||
Ivunika | 215 | |||||
4 | Ikigereranyo cyubu | A | 1250 1600 2000 2500 | |||
5 | Ikigereranyo cyigihe gito cyihangane nubu (RMS) | kA | 25 | 31.5 | ||
6 | Ikigereranyo cyo hejuru cyihanganira ikigezweho | 63 | 80 | |||
7 | Ikigereranyo kigufi cyumuzenguruko ucika (RMS) | 25 | 31.5 | |||
8 | Ikigereranyo kigufi-kizunguruka gikora ikigezweho (agaciro keza) | 63 | 80 | |||
9 | Ikigereranyo kigufi cyumuzunguruko | s | 4 | |||
10 | Urutonde rukurikirana ibikorwa | O-0.3s-CO-180s-CO | ||||
11 | Ikigereranyo kitari mucyiciro cy'isi amakosa yamenetse | kA | 21.7 | 27.4 | ||
12 | Ikigereranyo cya kabili yishyuza ikizamini cyo guhinduranya | A | 50 | |||
13 | Ikigereranyo kimwe / inyuma-kuri-capacitor banki yamenetse | 800/800 | ||||
14 | Ubuzima bwa mashini | ibihe | 10000 | |||
15 | Ibihe bigufi byumuzunguruko | ibihe | 30 | |||
16 | Secondary circuit 1 min power frequency kwihanganira voltage | 2000 | ||||
17 | Ikigereranyo cya voltage ikora | Gufunga igiceri | V | DC110 / 220, AC220 | ||
Gufungura igiceri | V | DC110 / 220, AC220 | ||||
18 | Ikigereranyo cya voltage ya moteri yo kubika ingufu | W | DC110 / 220, AC220 | |||
19 | Ikigereranyo cyingufu za moteri yo kubika ingufu | s | 250 | |||
20 | Igihe cyo kubika ingufu (voltage yagenwe) | s | ≤10 | |||
21 | Umuvuduko ukabije wa gaze ya SF6 (umuvuduko wa gauge kuri 20 ° C) | Mpa | 0.350+0.02 | |||
22 | Umuvuduko w'imenyesha | Mpa | 0.29 ± 0.01 | |||
23 | Umuvuduko muto wimikorere (guhagarika igitutu) | Mpa | 0.28 ± 0.01 | |||
24 | Igipimo cyumwaka | % | ≤0.5 | |||
25 | Ibirungo bya gaze | μL / L. | 50150 | |||
26 | Kwimura inkoni | mm | ≥78 | |||
27 | Umwanya | mm | 50 ± 1.5 | |||
28 | Igihe cyo gufungura | ms | 60 ~ 78 | |||
29 | Igihe cyo gusoza | ms | 65 ~ 95 | |||
30 | Ibyiciro bitatu byo gufunga no gufungura ntabwo arigihe | ≤5 | ||||
31 | Impuzandengo yo gufungura umuvuduko (muri 10m nyuma yigice) | ms | 2.2 ~ 2.8 | |||
32 | Impuzandengo yo gufunga umuvuduko (muri 10m nyuma yigice cya kabiri) | ms | ≥1.5 | |||
33 | Kurwanya imiyoboro nyamukuru | μΩ | ≤32 (Ikarita) | ≤20 (Ubwoko buhamye) |
Imiterere nyamukuru
![5](http://www.gpswitchgear.com/uploads/514.jpg)