12 17.5 24kV Imbere ya Vacuum Yumuzenguruko, GPVN-E Urukurikirane
Imiterere y'ibidukikije
Ubushyuhe bwibidukikije: -25 ℃ ~ + 45 ℃, impuzandengo ya buri munsi: ≤35 ℃
Uburebure: 1000m (Bisanzwe);irashobora kugera kuri 4500m yo gutumiza bidasanzwe;
Ubushuhe bugereranije: impuzandengo ya buri munsi ≤95%, impuzandengo ya buri kwezi ≤ 90%;
Imbaraga z’umutingito degree8;
Ibihe byakoreshwa bigomba kuba bitarimo umuriro, ibisasu, ruswa hamwe no kunyeganyega gukabije.
Icyitegererezo
![10](http://www.gpswitchgear.com/uploads/107.jpg)
GPVN -12Kv / 17.5kV Imbere mu nzu AC Umuvuduko mwinshi Umuyoboro wumuzunguruko
Ibisobanuro bya tekiniki
Oya. | Ingingo | Igice | Amakuru | ||||||
1 | Ikigereranyo cya voltage | kV | 7.2 ~ 12 (15 / 17.5) | ||||||
2 | Ikigereranyo cyagenwe | Hz | 50/60 | ||||||
3 | Ikigereranyo cyubu | A | 630.1000.1250 | 1600 | 2000,2500,3150 | 4000 | |||
4 | Ikigereranyo kigufi-kizunguruka kumeneka | kA | 20 | 25 | 31.5 | 31.5 | 40 | 40 | 50 |
5 | Ikigereranyo kigufi-kizunguruka gikora amashanyarazi | kA | 50 | 63 | 80 | 80 | 100 | 100 | 125 |
6 | Ikigereranyo kigufi-cyihangane nubu | kA | 20 | 25 | 31.5 | 31.5 | 40 | 40 | 50 |
7 | Ikigereranyo cyo hejuru cyihanganira ikigezweho | kA | 50 | 63 | 80 | 80 | 100 | 100 | 125 |
8 | Ikigereranyo cyo gukuramo kumeneka | kA | 12.6 | 12.6 | 16 | 16 | 20 | ||
9 | Ikigereranyo kitari mucyiciro cyo gutaka amakosa yamenetse | kA | 17.4 | 21.7 | 27.4 | 27.4 | 34.7 | 34.7 | 43.5 |
10 | Ikigereranyo kigufi-kizunguruka kumena igihe cyo kumena | Ibihe | 50 | 30 | 30 | 12 | |||
11 | Urutonde rukurikirana | O-0.3s-CO-180s-CO | O-180s-CO-180s-CO | ||||||
12 | Ikigereranyo cyo kumena amashanyarazi ya banki imwe ya capacitor | A | 630 | ||||||
13 | Ikigereranyo cyo kumena inyuma yinyuma kuri banki ya capacitor | A | 400 | ||||||
14 | 1min.Imbaraga zumuriro zihanganira voltage | kV | Icyiciro kugeza ku cyiciro / ku isi: 42, hejuru yugurura: 48 | ||||||
15 | Inkuba ihangane na voltage | kV | Icyiciro kugeza ku cyiciro / ku isi: 75, hakurya yugurura: 85 | ||||||
16 | Ubuzima bwa mashini | Ibihe | 20000 | ||||||
17 | Igihe cyo gusoza | ms | ≤75 | ||||||
18 | Igihe cyo gufungura | ms | ≤60 | ||||||
19 | Igihe cyo kubika ingufu munsi ya voltage yagenwe | s | ≤10 |
Urucacagu Igipimo cya GPVN-12E
![20](http://www.gpswitchgear.com/uploads/20.jpg)
![30](http://www.gpswitchgear.com/uploads/30.jpg)
GPVN-24 □ Imbere mu nzu AC Umuvuduko mwinshi wa Vacuum yamashanyarazi
Ibisobanuro bya tekiniki
Oya. | Ingingo | Igice | Amakuru | |||
1 | Ikigereranyo cya voltage | kV | 24 | |||
2 | Ikigereranyo cyagenwe | Hz | 50/60 | |||
3 | Ikigereranyo cyubu | A | 630 1250 1600 2000 2500 3150 4000 | |||
4 | Ikigereranyo kigufi-kizunguruka kumeneka | kA | 20 | 25 | 31.5 | 31.5 |
5 | Ikigereranyo kigufi-kizunguruka gikora amashanyarazi | kA | 50 | 63 | 80 | 80 |
6 | Ikigereranyo kigufi-cyumuzingi cyihanganira ikigezweho (4s) | kA | 20 | 25 | 31.5 | 31.5 |
7 | Ikigereranyo cyo hejuru cyihanganira ikigezweho | kA | 50 | 63 | 80 | 80 |
8 | Ikigereranyo cyo hanze-intambwe yo kumena ikigezweho | kA |
|
| 12.6 | 12.6 |
9 | Ikigereranyo cyo kumena amashanyarazi yo hanze yicyiciro cyisi | kA | 17.4 | 21.7 | 27.4 | 27.4 |
10 | Ikigereranyo cyo kumena ibihe bigufi byumuzunguruko | Ibihe | 50 | |||
11 | Urutonde rukurikirana |
| O-0.3s-CO-180s-CO | |||
12 | Ikigereranyo cyo kumena amashanyarazi ya banki imwe ya capacitor | A | 630 | |||
13 | Ikigereranyo cyo kumena imiyoboro yinyuma-yinyuma ya banki | A | 400 | |||
14 | 1min.Imbaraga zumuriro zihanganira voltage | kV | 50 | |||
15 | Inkuba ihangane na voltage | kV | 125 | |||
16 | Ubuzima bwa mashini | Ibihe | 20000 | |||
17 | Igihe cyo gusoza | ms | 75 | |||
18 | Igihe cyo gufungura | ms | 60 | |||
19 | Igihe cyo kubika munsi ya voltage yagenwe | s | 10 |
Igipimo cya GPVN-24E / (630 ~ 1250A) Kumena
![40](http://www.gpswitchgear.com/uploads/40.jpg)
Igipimo cya GPVN-24E / (1600 ~ 3150A) Kumena
![50](http://www.gpswitchgear.com/uploads/50.jpg)